火宅危险性较高的房间或场所

网址:www.gxgzx.com时间:2024-03-26 15:27:40(部分内容来源于网络,不代表本站观点)

火宅危险性较高的房间或场所(公建内的厨房、民用建筑附属库房等)

1) The doors of the evacuation stairwell and front room of the garage and repair garage should be Class B fire doors and should be opened in the evacuation direction.
1)汽车库、修车库的疏散楼梯楼梯间和前室的门应采用乙级防火门,并应向疏散方向开启。

2) In addition to the kitchen in the residential building, the public kitchen in the dormitory and apartment buildings and the kitchen in other buildings, the attached warehouse in the civil building, the auxiliary room of the theater backstage, etc., should be separated from other parts by fireproof partition wall with a fire resistance limit of not less than 2.00h, and the doors and Windows on the wall should be Class B fire doors and Windows. If it is really difficult, fire rolling curtains can be used.
2)除居住建筑中套内的厨房外,宿舍、公寓建筑中的公共厨房和其他建筑内的厨房,民用建筑内的附属库房,剧场后台的辅助用房等应采用耐火ji限不低于2.00h的防火隔墙与其他部位分隔,墙上的门、窗应采用乙级防火门、窗,确有困难时,可采用防火卷帘。

4. Doors of rooms (places) used by vulnerable groups (operating rooms, delivery rooms, etc.)
4. 弱势群体使用的房间(场所)门(手术室、产房等)

Operating rooms or operation departments, delivery rooms, intensive care units, rooms for valuable and precise medical equipment, storage rooms, laboratories, film rooms, etc., nurseries, children's rooms in kindergartens, children's play halls and other children's activity places attached to the buildings, and care facilities for the elderly,
医疗建筑内的手术室或手术部、产房、重症监护室、贵重精密医疗装备用房、储藏间、实验室、胶片室等,附设在建筑内的托儿所、幼儿园的儿童用房和儿童游乐厅等儿童活动场所、老年人照料设施,

The fire partition wall with a fire resistance limit of not less than 2.00h and the floor plate with 1.00h should be separated from other places or parts, and the doors and Windows that must be set up on the wall should be Class B fire doors and Windows.
应采用耐火ji限不低于2.00h的防火隔墙和1.00h的楼板与其他场所或部位分隔,墙上必须设置的门、窗应采用乙级防火门、窗。

5. Same function control scale partition (hospital nursing units, etc.)
5. 同功能控制规模分区(医院的护理单元间等)

The adjacent nursing units in the ward building of the hospital and nursing home shall be separated by fireproof partition walls with a fire resistance limit of not less than 2.00h, the doors on the partition walls shall adopt Class B fire doors, and the fire doors set on the walkway shall adopt normally open fire doors.
医院和疗养院的病房楼内相邻护理单元之间应采用耐火ji限不低于2.00h的防火隔墙分隔,隔墙上的门应采用乙级防火门,设置在走道上的防火门应采用常开防火门。

6. Equipment room (fire control room, etc.)
6. 设备用房(消防控制室等)